MCJB-1066 Relay Protection Tester

Model: MCJB-1066 Quantity: 1 set Manufacturer: Hubei MECI Electric Power Equipment Co., Ltd

Category: Relay Protection Tester

Keywords: MCJB-1066 Relay Protection Tester

Product Overview

Product Features

  • The main features of the microcomputer-based relay protection tester are as follows:
  • Equipped with the user-friendly Windows XP operating system, the human-machine interface is intuitive and easy to operate, enabling quick and efficient task completion. To further enhance usability, a wide range of keyboard shortcuts have been defined, allowing users to perform operations with a single key press.
  • High-performance embedded industrial control computers paired with large, high-resolution color TFT LCD displays provide rich, intuitive information, including the equipment’s current operating status, prompts for the next step, and various help messages.
  • Equipped with an ultra-thin industrial keyboard and a touch-enabled mouse, it allows users to perform various operations via the keyboard or mouse just as they would on a standard PC.
  • Equipped with an external USB interface, it enables convenient data access and software maintenance.
  • All test items can be completed without the need for any external equipment; test data are automatically displayed and recorded, and vector diagrams and characteristic curves are generated.
  • A high-performance D/A converter is employed, delivering waveforms with high accuracy and excellent linearity, as well as superior transient response and amplitude-frequency characteristics. Waveform accuracy and other performance specifications are consistently met across the entire measurement range.
  • It can directly output AC voltage, AC current, DC voltage, and DC current, with adjustable amplitude, phase angle, and frequency.
  • The power amplification stage employs a new high-power, high-fidelity linear amplifier circuit, delivering substantial output power with minimal ripple and interference. Even at maximum output current, the waveform remains undistorted and free of clipping.
  • The digital input interface can automatically accommodate both passive (dry-contact) and active inputs, and can also automatically adapt to the polarity of active inputs, operating reliably within an input voltage range of ±250 V.
  • It can perform a wide range of complex verification tasks, conveniently test and scan various protection setting values, store test data in real time, display vector diagrams, print reports, and more.
  • It features a meticulously engineered chassis design that is compact, offers excellent heat dissipation, is lightweight, easy to carry, and facilitates convenient flow testing.
  • The instrument features self-protection functionality, a well-designed thermal management system, robust and comprehensive protection measures, soft-start power supply, as well as built-in fault self-diagnosis and interlock capabilities.

Technical Specifications

AC current source

  1. Current Source with a Common Neutral Point for Six Phases Current rise and fall time < 100 microseconds
  2. Maximum output power: 300 VA per phase
  3. Output accuracy:
  4. Resolution:
  5. Single-phase continuous output time:

0.1A ~ 1 A Accuracy

±5 mA

1 A ~ 10 A Accuracy

plus or minus 0.2%

10 A ~ 30A accuracy

plus or minus 0.2%

0.1A ~ 10 A Resolving power

1mA

10 A ~ 30A resolution

5mA

0.1 A ~ 10 A Output time

No time limit

10 A ~ 20 A Output time

≥60 seconds

20 A ~ 30 A Output time

≥15 seconds

 

1.2.2 AC voltage source

  1. Voltage source with a common neutral point for six phases Current rise and fall time < 100 microseconds
  1. Maximum output power: ≥75 VA/Phase
  1. Output accuracy:
  2. Resolution:

1 Accuracy of V~5V

±10 mV

Accuracy from 5V to 125V

plus or minus 0.2%

1 V–5V resolution

1mV

5V to 125V resolution

5 millivolt

 

1.2.3 DC current source

  1. Single-phase output range -10A~ + 10 A or 0–20 A
  2. Maximum output power: 200 VA per phase
  3. Output accuracy:
  4. Resolution: 5m A

Accuracy of ±0.1 A to ±2 A

±10 mA

Accuracy of ±2 A to ±10 A

plus or minus 0.5%

 

1.2.4 DC voltage source

  1. DC Voltage Output Range -150V to +15 0V or 0–30 0V
  2. Maximum output power: greater than or equal to 100VA
  3. Output accuracy:
  4. Resolution:

Accuracy from ±1 V to ±5 V

±20 mV

Accuracy from ±5 V to ±150 V

plus or minus 0.5%

Resolution of ±1 V to ±5 V

5mV

Resolution: ±5 V to ±150 V

10 millivolt

 

1.2.5 Delivery Flow voltage and current source angle

  1. Phase angle range: 0 °~ 360°
  2. Accuracy: plus or minus 0.
  3. Resolution: 0. 01°

 

1.2.6 Delivery Flow voltage, current source frequency

  1. Frequency range: 10–15 00Hz
  2. Output accuracy:
  3. Resolution: 0.001 Hz
  4. Can be stacked 2 ~ 20 harmonic components of arbitrary amplitude and DC component

10Hz ~ 65Hz

±0.001 Hz

65Hz ~ 1500 Hertz

±0.02 Hz

 

1.2.7 Timing Accuracy

1 ms to 1 s

±10 ms

1S ~ 999999S

plus or minus 0.2%

 

1.2.8 Input Quantity

  1. 8 Independent switch contact input for the circuit, with automatic polarity detection of powered contacts.
  2. Compatible with dry contacts and 15V ~ 250V Powered contact

 

1.2.9 Number of Issuances

  1. 4 Programmable switch dry-contact output
  2. Contact capacity 250VDC0.5A  or 250VAC0.5A

 

1.2.10 Synchronization

Voltage-current synchronicity ≤50 mu S

 

1.2.11 Power Supply

  1. AC Input Voltage

Rated value: 220V ± 10%

Baseline value: 220V ± 2%

  1. AC power supply frequency:

Rated value: 50 Hz ± 10%

Baseline value: 50 Hz ± 2%

 

1.2.12 Operating Environment Conditions

  1. Ambient temperature: – 10℃ to +40℃
  2. Relative humidity: ≤90%
  3. Atmosphere Pressure: 80–110 kPa

 

1.2.13 Enclosure Dimensions and Weight

  1. Box dimensions (Long (Width × Height × Depth): 420 mm × 190 mm × 470 mm
  2. Weight: 23 kilograms

Related Products

New Product Recommendations

Product Center

Power Quality, Harmonic Analyzer

Metrological verification device

Relay Protection Tester

Transformer Testing

Capacitors and Generators

Product Inquiry

Leave your contact information to receive a free product quote.

Submit Message