MC-XBII Power Harmonic Tester

MC-XBII Power Harmonic Tester

Model: MC-XBII Quantity: 1 set Manufacturer: Hubei MECI Electric Power Equipment Co., Ltd

Category: Power Quality, Harmonic Analyzer

Keywords: MC-XBII Power Harmonic Tester

Product Overview

With the rapid development of China’s national economy, electricity demand has increased dramatically, particularly due to the continuous growth in the capacity of impulsive and nonlinear loads, which has led to waveform distortion in the power grid. The MC-XBII Power Harmonic Analyzer, launched by our company (hereinafter referred to as MC-XBII), is a high-performance instrument for measuring power harmonics. It employs a DSP+ARM core architecture, resulting in a more compact design and more convenient operation and display.

Product Features

  • 3.1 Safe and Reliable

The voltage input utilizes a high-voltage isolation module, while the current input employs an AC current clamp to ensure safe isolation between the input signal and the measurement system, thereby significantly enhancing the MC-XBII’s immunity to interference.

  • 3.2 Ease of Use

Portable design, compact size and lightweight, with a built-in high-performance lithium battery—no external power supply required.

  • 3.3 High Accuracy

The harmonics comply with the requirements for Class B instruments as specified in the national standard. A high-precision 16-bit A/D converter is employed, with simultaneous sampling at a rate of 12.8 kHz.

  • 3.4 Powerful Software Functions

By employing a DSP+ARM core, the MC-XBII delivers high processing speed and robust software functionality, making it well-suited for complex testing and data-processing tasks and significantly enhancing testing efficiency and performance.

  • 3.5 Numerous test parameters

Power quality parameters specified in the national standard, including system frequency, grid harmonics, fundamental voltage RMS and true RMS values, fundamental current RMS and true RMS values, active power, reactive power, harmonics from the 2nd to the 30th order, and true power factor.

  • 3.6 USB Interface

Data can be stored on a USB flash drive.

Technical Specifications

Frequency Measurement

Measurement range: 45–55 Hz, with a center frequency of 50 Hz; measurement conditions: the fundamental component of the signal shall be no less than 80% of full scale.

Measurement error: ≤0.02 Hz

Input voltage range: 10–450 V

Input current range: 5 A

Fundamental voltage and current amplitudes: allowable error for fundamental voltage ≤ 0.5% of full scale; allowable error for fundamental current ≤ 1% of full scale.

Measurement error of the phase difference between fundamental voltage and current: ≤0.5°

Harmonic voltage distortion measurement error: ≤0.1%

Harmonic current distortion measurement error: ≤0.2%

Power deviation: ≤0.5%

Operating time: The internal battery provides 8 hours of continuous operation.

Related Products